Biological treatment plant alarm: what it means and what to do

A biological wastewater treatment plant (BIO plant) alarm tells you the plant is no longer working normally: most often the compressor has stopped, the power supply has been cut, the level in the tank is too high or the controller is reminding you about maintenance. Without an air supply the aerobic bacteria cannot work, so you must not simply switch the alarm off and forget about it. Below you'll find how to read the signal and what to check yourself before you request maintenance or a repair.

Prepared by Septiķis Rīga · Updated 30 October 2026 · Sources: 4

After you submit the form, we contact you within 5 minutes

Get a price

Name, phone and address are required. The rest helps us give a more accurate price.

After you submit the form, we contact you within 5 minutes

The most common causes of an alarm

Signal Possible cause What to do
The display is dark or reports a power failure The circuit breaker has tripped, the plug is out of the socket, a power cut Check the distribution board and the connection; once power is back, make sure the compressor is running again
Compressor error Worn membrane, clogged air filter, overheating, faulty compressor Listen for the compressor humming; if it isn't, it needs maintenance or repair
High level Clogged outlet, discharge pump not working, overload or rainwater flowing in Use less water and check the outlet; pumping out may be needed
Maintenance reminder Time to clean the filter, replace the membrane or carry out routine maintenance Not an emergency, but request maintenance soon
Valve or cycle error Faulty valve module or control unit Maintenance or repair

AUGUST controller lights

The AUGUST AT technical passport describes the signals as follows:

  • a steady green light means the compressor has been stopped temporarily; this is not a fault;
  • a flashing green light means the compressor is running;
  • a steady red light means the compressor or an auxiliary device is disconnected or faulty;
  • a flashing red light with a sound means a power failure. The signal can go on for several hours, as long as the battery lasts. When power returns, the controller switches on after 2 minutes.

Reminders can also appear on the display: REPLACE FILTER (after six months the compressor filter must be cleaned or replaced) and CHANGE MEMBRANE (after a year the membrane must be replaced). The passport provides that if the controller fails, the compressor can be disconnected from the controller and plugged straight into the mains so that the plant keeps getting air. Under the passport, inspection and maintenance are carried out by AUGUST specialists or authorised representatives.

Source: AUGUST technical passport (lzt.lv), sections “Optical signalling” and “Controller notifications about technical maintenance”. Checked on 30 October 2026.

The AQUABLOC control unit

The AQUABLOC control unit checks the condition and connection of the compressor, the valve module and the work cycle by itself at least once a day. The audible alarm sounds only between 8:00 and 20:00; pressing any button silences it for 24 hours if the fault persists. Built-in service timers remind you about maintenance: for the plant after 365 days, for the compressor after 7,000 working hours.

Source: AQUABLOC user manual 2026 (aquabin.pl), description of the control unit. Checked on 30 October 2026.

What to do in the first few hours

  1. Read the message Take a photo of the display or write down which light is on and how.
  2. Check the power Look at the circuit breaker in the distribution board, and check the socket and the extension cable, if there is one.
  3. Listen to the compressor Is it humming? Is it too hot, or is there unusual vibration? According to the PURA passport, these things should be checked regularly.
  4. Open the lid There should be fine bubbles in the aeration chamber. If there are none, or the level is close to overflowing, the problem is serious.
  5. Use less water While the plant isn't working, every litre leaves untreated or raises the level.
  6. Don't switch programmes The AUGUST passport states that changing the programme often is not recommended. It won't fix a technical fault.
  7. Send a request Give the manufacturer, the model, the message on the display and when the plant was last serviced.

Why you must not ignore an alarm

When the compressor stops, the plant stops treating, and poorly treated water leaves through the outlet into a ditch or the ground. National regulations require the owner of a BIO plant to ensure that the sludge is active and that there are no conditions that worsen treatment, and to carry out extraordinary maintenance after a breakdown. A copy of the maintenance document must be submitted to the keeper of the register within a month.

Source: Cabinet Regulation No. 384, points 4.3.2, 4.3.3 and 15.3 (likumi.lv). Checked on 30 October 2026.

The most common repairs

  • replacing the compressor membrane (AUGUST provides for it once a year);
  • cleaning or replacing the air filter (AUGUST: every 6 months);
  • replacing the compressor if it overheats or doesn't build up pressure;
  • replacing the float switch or the discharge pump;
  • cleaning clogged airlifts and pipes;
  • pumping out surplus sludge if there is too much of it.

Read more about the work in biological treatment plant repair. Maintenance of specific models: AUGUST AT-6, PURA.

How much it costs

Routine BIO plant maintenance costs from €160. The cost of a repair depends on what needs replacing: the membrane, the compressor, the pump or the control unit. Give the model and the message on the display in your request, and we can tell you an approximate price before we travel out.

Sources

  1. AUGUST: light signals, power failure and 2 min, battery, REPLACE FILTER 6 months, CHANGE MEMBRANE 1 year, compressor plugged straight into the mains, changing programmes not recommended, maintenance only by authorised persons checked 30 October 2026
  2. AQUABLOC: daily self-test, sound 8:00–20:00, silencing for 24 h, service timers 365 days and 7,000 h checked 30 October 2026
  3. PURA: check the blower regularly (switched on, not hot, no vibration) checked 30 October 2026
  4. Cabinet Regulation No. 384: active sludge (point 4.3.2), maintenance and extraordinary maintenance after a breakdown (point 4.3.3), copy of the document within a month (point 15.3) checked 30 October 2026

Request BIO plant maintenance or repair

Give the manufacturer and model, which light is on or what message is on the display, and when the plant was last serviced.

Get a price

We contact you within 5 minutes of your request.

Related prices
Service Price
BIO plant maintenance from €160
Surplus sludge pumping up to 4 m³ from €75
Travel outside Riga ~€1/km

Frequently asked questions

Can the alarm sound be switched off?

Yes. On the AUGUST controller you can do it with a button; on the AQUABLOC control unit, any button silences it for 24 hours. But switching off the sound does not remove the cause.

The alarm went off after a power cut. What should I do?

Make sure the controller has switched back on and the compressor is running once the power is restored. If the battery was heavily discharged, the AUGUST passport advises checking and setting the correct time.

The compressor is running, but the alarm light is on. Why?

Often the reason is a high level (a clogged outlet or a discharge pump that isn't working), or the controller is reminding you about maintenance. Look at the message on the display and the level in the tank.

Can I replace the membrane myself?

Some manufacturers provide that maintenance is carried out only by an authorised service, and national regulations entrust routine maintenance to a suitable company. Check your plant's passport before you replace anything yourself.

Send a request

A specialist contacts you within 5 minutes to confirm the job and the price.

Get a price

Name, phone and address are required. The rest helps us give a more accurate price.

After you submit the form, we contact you within 5 minutes

Get a price we contact you within 5 minutes